机械系统警报参考

对于数据中心的机械资产,机械系统警报会通知您所有底层数据点的警报情况。

早期烟气检测

整个数据中心都安装了能够探测烟雾和火灾的设备。当这些探测器感应到火灾或烟雾时,就会触发系统警报并发出警报。

Data PointDefinitionValuesMeaningsSystem Alert Conditions
AlarmIndicates the VESDA system has detected smoke.NORMALNORMAL: No system alert presentALARM
ALARMALARM: Asset has a system alert
FaultIndicates the operation of VESDA falls outside defined parameters. VESDA might or might not continue to operate when a fault is present.NORMALNORMAL: No fault presentFAULT
ALARMALARM: Asset has a fault

火灾报警系统

整个数据中心都安装了能够探测烟雾和火灾的设备。当这些探测器感应到火灾或烟雾时,就会触发系统警报并发出警报。

Data PointDefinitionValuesMeaningsSystem Alert Conditions
AlarmIndicates the fire alarm system has detected a fire.NORMALNORMAL: No fault presentALARM
ALARMALARM: Asset has a fault
TroubleIndicates the operation of the fire alarm system falls outside defined parameters.NORMALNORMAL: No system alert presentTROUBLE
TROUBLEALARM: Asset readings are outside accepted parameters

冷却厂

这些设备旨在维持适合数据中心运行的环境条件。系统必须将数据中心设备产生的热量去除,并将其转移到散热器。

Data PointDefinitionValuesMeaningsSystem Alert Conditions
Primary Chilled Water Supply TemperatureIndicates the temperature of the primary water supply.Temperature + UOM preferenceSetpoint +10% for 300 seconds or Setpoint +/- 20% for 180 seconds (setpoint varies site to site (6-12 deg C) due to site cooling design)VALUE
Chilled Water Storage Level OKIndicates the water level in the water storage tank.ALARMALARM: Asset has a system alertALARM

渗漏检测

数据中心内检测水、腐蚀性化学品或其他腐蚀性液体泄漏的设备(如与天气有关的液体入侵、有问题的管道以及屋顶和窗户的结构故障造成的潮湿)。

Data PointDefinitionValuesMeaningsSystem Alert Conditions
Leak Detected Somewhere in IBXIndicates that moisture level has exceeded established parameters.NORMALNORMAL: No system alert presentALARM
ALARMALARM: Asset has a system alert