Electrical System Alerts Reference

For the electrical assets in your data center, Electrical System Alerts notify you of the alarm conditions of all the underlying data points.

Generators

Data PointDefinitionValuesDescriptionSystem Alert Conditions
Fuel HoursNumber of hours generators can run with fuel on hand at current IBX loadActual ValueNumber of hours generators can run with fuel on hand at current IBX loadValue ≤12 hours
SummaryCombined summary of running status, connection status, hand/ auto status, and alarm statusREADY TO START, AUTOGenerator is ready to run automatically in auto mode
STOPPED, NOT IN AUTOGenerator is stopped and not in auto modeSTOPPED, NOT IN AUTO
STOPPED, AUTO, ALARMGenerator is stopped while in auto modeSTOPPED, AUTO, ALARM
STOPPED, NOT IN AUTO, ALARMGenerator is stopped while not in auto modeSTOPPED, NOT IN AUTO, ALARM
RUNNING, NON- EMERGENCY SERVICEGenerator is running and not supplying power to the IBX load in auto mode
RUNNING, NON- EMERGENCY SERVICE, NOT IN AUTOGenerator is running and not supplying power to the IBX load while not in auto mode (hand mode)
RUNNING, NON- EMERGENCY SERVICE, ALARMGenerator is running and not supplying power to the IBX load in auto mode, in an alarm stateRUNNING, NONEMERGENCY SERVICE, ALARM
RUNNING, NON- EMERGENCY SERVICE, NOT IN AUTO, ALARMGenerator is running and not supplying power to the IBX load while not in auto mode (hand mode), in an alarm stateRUNNING, NONEMERGENCY SERVICE, NOT IN AUTO, ALARM
RUNNING, EMERGENCY SERVICEGenerator is running and supplying power to the IBX load in auto modeRUNNING, EMERGENCY SERVICE
RUNNING, EMERGENCY SERVICE, NOT IN AUTOGenerator is running and supplying power to the IBX load while not in auto mode (hand mode)RUNNING, EMERGENCY SERVICE, NOT IN AUTO
RUNNING, EMERGENCY SERVICE, ALARMGenerator is running and supplying power to the IBX load in auto mode in an alarm stateRUNNING, EMERGENCY SERVICE, ALARM
RUNNING, EMERGENCY SERVICE, NOT IN AUTO, ALARMGenerator is running and supplying power to the IBX load while not in auto mode (hand mode) in an alarm stateRUNNING, EMERGENCY SERVICE, NOT IN AUTO, ALARM
VoltageIndicates voltage is outside rangeAlarmThe voltage alarm is active when the generator voltage is running outside the normal rangeThe normal range is +/- 20% of the Nominal Voltage (standard operating voltage)

Automatic Transfer Switch (ATS)

Data PointDefinitionValuesDescriptionSystem Alert Conditions
Normal SourceIndicates whether normal power source is available and within tolerancesAVAILABLE, UNAVAILABLEAVAILABLE: Normal power source is available and within tolerances UNAVAILABLE: Normal power source is not available or is available but outside tolerancesUNAVAILABLE
Switch On EmergencyIndicates whether load is connected to the emergency power sourceYES, NOYES: Output of ATS is sourced from emergency power source NO: Output of ATS is not sourced from emergency power sourceYES

Power Distribution Unit (PDU)

Data PointDefinitionValuesDescriptionSystem Alert Conditions
Summary AlarmTriggered when the operation of the PDU falls outside defined parameters. PDU might, or might not be able to continue operations.NORMAL, ALARMNORMAL: No summary alarm present ALARM: Asset has a summary alarmALARM

Uninterruptible Power Supply (UPS)

Data PointDefinitionValuesDescriptionSystem Alert Conditions
Summary AlarmTriggered when the operation of the UPS falls outside of defined parameters and failure is imminentNORMAL, ALARMNORMAL: No summary alarm present and UPS failure is not imminent ALARM: A summary alarm is present and UPS failure is imminentALARM
Battery DischargeIndicates whether batteries are exclusively providing power to the UPS outputNORMAL, ALARMNORMAL: The load on batteries is within normal range ALARM: The load on batteries is not within normal rangeALARM
Load on BypassIndicates whether load is bypassing the UPSNORMAL, ALARMNORMAL: The UPS load is not bypassing the UPS ALARM: The UPS load is bypassing the UPSALARM
Low Battery AlarmIndicates the batteries are nearly depleted and UPS shutdown is imminentNORMAL, ALARMNORMAL: Battery power is within normal range ALARM: Battery power is below normal rangeALARM
Output OverloadIndicates whether the output of the UPS has exceeded system ratingNORMAL, ALARMNORMAL: UPS not overloaded ALARM: UPS overloadedALARM
Warning AlarmTriggered when the operation of the UPS falls outside of defined parameters and UPS critical functions can continue to operateNORMAL, ALARMNORMAL: No warning alarm present ALARM: Asset has a warning alarmALARM

Utility Power

Data PointDefinitionValuesDescriptionSystem Alert Conditions
Utility Power ServiceIndicates if utility power is available and within tolerancesNORMAL ALARMNORMAL: Utility power is available within tolerances ALARM: Utility power is not available or is available but outside tolerancesALARM

Automatic Static Transfer Switch (ASTS)

Data PointDefinitionValuesDescriptionSystem Alert Conditions
AlarmGeneral alarm indicating if an alarm trigger has been met and should therefore indicate an alarm condition stateNORMAL, ALARMNORMAL: No general alarm present ALARM: General alarm is presentALARM
Load on Source 1Indicates electrical load is connected to the primary electrical sourceYES, NOYES: Output of ASTS is connected to the primary electrical source NO: Output of ASTS is not connected to the primary electrical sourceNONE (Not an alarmed point; informational only.)
Load on Source 2Indicates electrical load is connected to secondary electrical sourceYES, NOYES: Output of ASTS is connected to the secondary electrical source NO: Output of ASTS is not connected to the secondary electrical sourceNONE (Not an alarmed point; informational only.)
Source 1 FailureIndicates whether the primary electrical source is available and within tolerancesNORMAL, ALARMNORMAL: Primary electrical source is available and within tolerances ALARM: Primary electrical source is unavailable or is available but outside tolerancesALARM
Source 2 FailureIndicates whether the secondary electrical source is available and within tolerancesNORMAL, ALARMNORMAL: Secondary electrical source is available and stable ALARM: Secondary electrical source is unavailable or is available but outside tolerancesALARM