Available Data Points

This list shows which points the Subscriptions API will make available given the right permissions are enabled. If the data point exists, and is mapped to the appropriate customers, they will be sent to the subscription's endpoint. If certain data points that should be included in a subscription are missing, open a ticket through the Customer Portal.

note

X‑Scale is for customers who are the sole tenant of upstream infrastructure. The equipment is owned and operated by Equinix but is used exclusively by a single customer, with no shared upstream systems. This typically applies when a customer has leased an entire building or an entire data hall within a building.

API+ applies to shared environments, where upstream infrastructure and systems are used by multiple customers.

Asset TypeDisplay NameData TypeX-Scale
Air Handling UnitFan StatusBool
Air Handling UnitReturn air temperatureFloat
Air Handling UnitSupply air temperatureFloat
Computer Room Air HandlerGeneral AlarmBool
Computer Room Air HandlerFan StatusBool
Computer Room Air HandlerSupply air temperatureFloat
Computer Room Air HandlerReturn air temperatureFloat
Computer Room Air HandlerEntering water temperatureFloat
Computer Room Air HandlerResilientBool
Computer Room Air ConditionerGeneral AlarmBool
Computer Room Air ConditionerFan StatusBool
Computer Room Air ConditionerSupply air temperatureFloat
Computer Room Air ConditionerReturn air temperatureFloat
Computer Room Air ConditionerCompressor high head pressure (Stage 1)Bool
Computer Room Air ConditionerCompressor high head pressure (Stage 2)Float
Computer Room Air ConditionerResilientBool
Cooling PlantGeneral AlarmBool
Cooling PlantEntering water temperatureFloat
Cooling PlantLeaving water temperatureFloat
Cooling PlantFan run statusBool
Cooling PlantFan failureBool
Cooling PlantPrimary Chilled water supply temperatureFloat
Cooling TowerEntering water temperatureFloat
Cooling TowerFan run statusBool
Chilled Water PumpPump run statusBool
Chilled Water PumpPump HOA statusBool
Chilled Water PumpPump failureBool
Condenser Water PumpPump run statusBool
Condenser Water PumpPump HOA statusBool
Condenser Water PumpPump failureBool
ChillerChiller statusBool
ChillerChiller HOA statusBool
ChillerChiller failureBool
ChillerChiller FailedBool
ChillerEvaporator entering water temperatureFloat
ChillerEvaporator leaving water temperatureFloat
ChillerCondenser entering water temperatureFloat
ChillerCondenser leaving water temperatureFloat
ChillerPrimary Chilled Water Return TempBool
ChillerPrimary Chilled Water Supply TempBool
ChillerResilientBool
Cooling Distribution Unit (CDU)Unit statusBool
Cooling Distribution Unit (CDU)General AlarmBool
Cooling Distribution Unit (CDU)Primary flow rateFloat
Cooling Distribution Unit (CDU)Primary supply temperatureFloat
Cooling Distribution Unit (CDU)Primary return temperatureFloat
Cooling Distribution Unit (CDU)Secondary flow rateFloat
Cooling Distribution Unit (CDU)Secondary Supply PressureFloat
Cooling Distribution Unit (CDU)Secondary Return PressureFloat
Cooling Distribution Unit (CDU)Secondary supply temperatureFloat
Cooling Distribution Unit (CDU)Secondary return temperatureFloat

Electrical Assets​

Asset TypeDisplay NameData TypeX-Scale
Automatic Static Transfer Switch (ASTS)AlarmBool
Automatic Static Transfer Switch (ASTS)Load on source 1Bool
Automatic Static Transfer Switch (ASTS)Load on source 2Bool
Automatic Static Transfer Switch (ASTS)Power Supply FaultBool
Automatic Static Transfer Switch (ASTS)Preferred SourceString
Automatic Static Transfer Switch (ASTS)Source 1 failureBool
Automatic Static Transfer Switch (ASTS)Source 2 failureBool
Automatic Transfer Switch (ATS)Emergency SourceBool
Automatic Transfer Switch (ATS)Normal sourceBool
Automatic Transfer Switch (ATS)Switch on normalBool
Automatic Transfer Switch (ATS)Switch on emergencyBool
Customer Billing Meter (CBM)Apparent powerFloat
Customer Billing Meter (CBM)CurrentFloat
Customer Billing Meter (CBM)Kilo Watt HourFloat64
Customer Billing Meter (CBM)Power FactorFloat
Customer Billing Meter (CBM)Real PowerFloat
Customer Billing Meter (CBM)VoltageFloat
GeneratorAlarmBool
GeneratorBattery Low Voltage AlarmBool
GeneratorCoolant High Temperature ShutdownBool
GeneratorEmergency Stop AlarmBool
GeneratorFail to Start AlarmBool
GeneratorFailure to CloseBool
GeneratorFrequencyFloat
GeneratorFrequency Over the LimitsBool
GeneratorFrequency Under the LimitsBool
GeneratorFuel Tank Fuel Level (Hours)Float
GeneratorGenerator OverloadBool
GeneratorNot in Auto AlarmBool
GeneratorOverspeed AlarmBool
GeneratorResilientBool
GeneratorRunning - Emergency OperationBool
GeneratorRunning - Non-Emergency OperationBool
GeneratorShutdown AlarmBool
GeneratorSummary AlarmInt
GeneratorVoltageFloat
GeneratorVoltage Over the LimitsBool
GeneratorReal Power TotalFloat☑
GeneratorReal Energy TotalFloat☑
Power Circuit (Retail Only)Apparent powerFloat
Power Circuit (Retail Only)CurrentFloat
Power Circuit (Retail Only)Power FactorFloat
Power Circuit (Retail Only)Real PowerFloat
Power Distribution Unit (PDU)Breaker Status (On/Off)Bool
Power Distribution Unit (PDU)Frequency Deviation AlarmBool
Power Distribution Unit (PDU)Over Voltage AlarmBool
Power Distribution Unit (PDU)Under Voltage AlarmBool
Power Distribution Unit (PDU)Power Factor TotalFloat
Power Distribution Unit (PDU)Summary AlarmBool
Power Meter (Generator, UPS, PDU, CBM)Current AFloat☑
Power Meter (Generator, UPS, PDU, CBM)Current BFloat☑
Power Meter (Generator, UPS, PDU, CBM)Current CFloat☑
Power Meter (Generator, UPS, PDU, CBM)FrequencyFloat
Power Meter (Generator, UPS, PDU, CBM)Power FactorFloat
Power Meter (Generator, UPS, PDU, CBM)Real Power TotalFloat☑
Power Meter (Generator, UPS, PDU, CBM)Real Energy TotalFloat☑
Uninterruptible Power Supply (UPS)Battery DischargeBool
Uninterruptible Power Supply (UPS)Battery Over TempBool
Uninterruptible Power Supply (UPS)Battery Time RemainingFloat
Uninterruptible Power Supply (UPS)Frequency OutputFloat
Uninterruptible Power Supply (UPS)Inverter FaultBool
Uninterruptible Power Supply (UPS)Inverter out of SynchronizationBool
Uninterruptible Power Supply (UPS)Low battery alarmBool
Uninterruptible Power Supply (UPS)Output OverloadBool
Uninterruptible Power Supply (UPS)Overload AlarmBool
Uninterruptible Power Supply (UPS)ResilientBool
Uninterruptible Power Supply (UPS)Static Bypass Voltage ABFloat
Uninterruptible Power Supply (UPS)Static Bypass Voltage BCFloat
Uninterruptible Power Supply (UPS)Static Bypass Voltage CAFloat
Uninterruptible Power Supply (UPS)System in AlarmBool
Uninterruptible Power Supply (UPS)UPS Load on BypassBool
Uninterruptible Power Supply (UPS)warning alarmBool
Utility ServiceUtility PowerBool

Other Assets​

Asset TypeDisplay NameData TypeX-Scale
Environmental SensorsTemperatureFloat
Environmental SensorsHumidityFloat
Fire, Smoke & Leak Detection SystemFire panel alarmBool
Fire, Smoke & Leak Detection SystemSmoke panel alarmBool
Fire, Smoke & Leak Detection SystemLeak detectionBool
Weather StationTemperatureFloat
Weather StationHumidityInt