Mechanical System Alerts Reference
For the mechanical assets in your data center, Mechanical System Alerts notify you of the alarm conditions of all the underlying data points.

Devices which can detect smoke and fire are installed throughout the data center. When these detectors sense fire or smoke, they sound an alarm from a triggered system alert.
Data Point |
Definition |
Values |
Meanings |
System Alert Conditions |
---|---|---|---|---|
Alarm |
Indicates the VESDA system has detected smoke. |
NORMAL |
NORMAL: No system alert present |
ALARM |
ALARM |
ALARM: Asset has a system alert |
|||
Fault |
Indicates the operation of VESDA falls outside defined parameters. VESDA might or might not continue to operate when a fault is present. |
NORMAL |
NORMAL: No fault present |
FAULT |
ALARM |
ALARM: Asset has a fault |

Devices which can detect smoke and fire are installed throughout the data center. When these detectors sense fire or smoke, they sound an alarm from a triggered system alert.
Data Point |
Definition |
Values |
Meanings |
System Alert Conditions |
---|---|---|---|---|
Alarm |
Indicates the fire alarm system has detected a fire. |
NORMAL |
NORMAL: No fault present |
ALARM |
ALARM |
ALARM: Asset has a fault |
|||
Trouble |
Indicates the operation of the fire alarm system falls outside defined parameters. |
NORMAL |
NORMAL: No system alert present |
TROUBLE |
TROUBLE |
ALARM: Asset readings are outside accepted parameters |

Devices designed to maintain environmental conditions suitable for data center operation. The heat produced by the data center equipment must be removed and transferred to a heat sink.
Data Point |
Definition |
Values |
Meanings |
System Alert Conditions |
---|---|---|---|---|
Primary Chilled Water Supply Temperature |
Indicates the temperature of the primary water supply. |
Temperature + UOM preference |
Setpoint +10% for 300 seconds or Setpoint +/- 20% for 180 seconds (setpoint varies site to site (6-12 deg C) due to site cooling design) |
VALUE |
Chilled Water Storage Level OK |
Indicates the water level in the water storage tank. |
ALARM |
ALARM: Asset has a system alert |
ALARM |

Devices in the data center that detect leaks from water, caustic chemicals, or other corrosive fluids (such as moisture from weather-related fluid intrusion, faulty piping, and structural failures of roofs and windows).
Data Point |
Definition |
Values |
Meanings |
System Alert Conditions |
---|---|---|---|---|
Leak Detected Somewhere in IBX |
Indicates that moisture level has exceeded established parameters. |
NORMAL |
NORMAL: No system alert present |
ALARM |
ALARM |
ALARM: Asset has a system alert |